sql

FN-CTM CITY TIE MODULE

CALL
Update Terakhir
05 Jul 2024
Pembelian Min
1 1
Kategori
HOCHIKI

Fire Suppression System



Standard Feature



• Interfaces Fire Alarm Control Panels to a Local Energy type City Tie monitoring circuit



• Integrates Fire Alarm Control Panel EOL device into module for supervision of interface wiring



• Wide operating voltage



• Power limited operation



• Transient protection



•Terminals accept up to 14 AWG wire



• Mounts to a standard 4" electrical back box



SPECIFICATIONS



Operating Voltage 12 ~ 30 VDC



Average Current Consumption 0mA (Standby)



Alarm Current 1A for 0.5 seconds



Ambient Temperature 32°F (0 C) ~ 120°F (49C)



Maximum Humidity 90% RH, non-condensing



Dimensions 4.2"W X 4.7"H X 1.1"D



Weight Approximately 3.0 ounces



Mounting 4" square electrical box DESCRIPTION



The FN-CTM City Tie Module is used to connect a Fire Alarm Control Panel to a Local Energy type City Tie Monitoring circuit. The FN-CTM City Tie Module circuit provides the power necessary to trip the Master Box Trip Coil when the Fire Alarm Control Panel goes into alarm. The City Tie Circuit is capable of providing 1A for 0.5 seconds to operate the Master Box Trip Coil. The wiring is supervised to the Master Box by placing the Fire Alarm Control Panel EOL device on the terminals of the FN-CTM City Tie Module.